Subsection (1)
Lift, Escalator and Passenger Conveyor Regulations 6(1)6(1)opening
The user shall ensure that every lift, escalator or passenger conveyor is inspected and tested in accordance with the relevant health and safety standards incorporated into these Regulations under section 44 of the Act—
Lift, Escalator and Passenger Conveyor Regulations 6(1)(a)6(1)(a)entry
before such lift, escalator or passenger conveyor is put into use for the first time; or
Lift, Escalator and Passenger Conveyor Regulations 6(1)(b)6(1)(b)entry
after any modification has been effected; or
Lift, Escalator and Passenger Conveyor Regulations 6(1)(c)6(1)(c)entry
after any failure has occurred; or
Lift, Escalator and Passenger Conveyor Regulations 6(1)(d)6(1)(d)entry
whenever there has been a change in the competent lift service provider; and
Lift, Escalator and Passenger Conveyor Regulations 6(1)(e)6(1)(e)entry
at intervals not exceeding 24 months thereafter, or at shorter intervals according to in-house risk assessment,
Lift, Escalator and Passenger Conveyor Regulations 6(1)6(1)closing
by an inspection service provider who shall complete a comprehensive report separately for each lift, escalator or passenger conveyor so inspected and tested, and such inspection service provider shall date and sign such report and submit it within 30 days to the user, who shall keep the report in a safe place and a copy of the report in the machine compartment.
Subsection (2)
Lift, Escalator and Passenger Conveyor Regulations 6(2)6(2)entry
If an inspection or test carried out by an inspection service provider on a lift, escalator or passenger conveyor shows that any defect or weakness exists whereby persons are endangered, the inspection service provider shall report such defect or weakness forthwith to the user, the competent lift service provider and the provincial director, and no person shall be conveyed or allowed to be conveyed in or on such lift, escalator or passenger conveyor until such defect has been rectified to the satisfaction of the inspection service provider.
Subsection (3)
Lift, Escalator and Passenger Conveyor Regulations 6(3)6(3)entry
If a comprehensive report in accordance with a health and safety standard incorporated into these Regulations under section 44 of the Act shows a defect or weakness not considered under subregulation (2) the user shall rectify such defect or weakness.
Subsection (4)
Lift, Escalator and Passenger Conveyor Regulations 6(4)6(4)opening
A comprehensive report for a lift, escalator or passenger conveyor shall be completed when—
Lift, Escalator and Passenger Conveyor Regulations 6(4)(a)6(4)(a)entry
the lift, escalator or conveyor is put into use for the first time;
Lift, Escalator and Passenger Conveyor Regulations 6(4)(b)6(4)(b)entry
any modification to the lift, escalator or conveyor has been effected;
Lift, Escalator and Passenger Conveyor Regulations 6(4)(c)6(4)(c)entry
a reportable incident in terms of section 24 of the Act occurs;
Lift, Escalator and Passenger Conveyor Regulations 6(4)(d)6(4)(d)entry
there is a change in the designated competent lift service provider; and
Lift, Escalator and Passenger Conveyor Regulations 6(4)(e)6(4)(e)entry
at intervals not exceeding 24 months thereafter.
Subsection (5)
Lift, Escalator and Passenger Conveyor Regulations 6(5)6(5)entry
When an inspection or a test is conducted by an inspection service provider the inspection service provider shall ensure that all the documents and records required in terms of regulation 8 are kept in good order and are up to date.
Subsection (6)
Lift, Escalator and Passenger Conveyor Regulations 6(6)6(6)entry
An inspector may at any reasonable time inspect any lift, escalator or passenger conveyor, and the user shall place, free of charge, at the disposal of the inspector any workmen and equipment that may be reasonably required by the inspector for the purpose of carrying out such inspection.
Subsection (7)
Lift, Escalator and Passenger Conveyor Regulations 6(7)6(7)entry